Temperature Transducers DIP configurable

TYPE LXT-811-D LXT-81U-D
Photo LXT-811-D LXT-81U-D
Schematic schematic-LXT-811-D schematic-LXT-81U-D
INPUT
Ressistance 0..1600 Ω
Voltage -5…140 mV
RTD sensor Pt100, Cu100, Ni100, Pt1000, user defined
Thermocouple B, J, K, N, R, S, user defined¹
Cold junction compensation (TC only) automatic / 0°C
Line compensation (RTD only) automatic / 0°C
OUTPUT
2-wire current loop 4…20 mA
Current output 0…5 mA / 4…20 mA / 0…20 mA
Voltage output 0…5 V / 0…10 V
POWER SUPPLY
From current loop checkboxico checkboxico
Supply voltage range 10…30 VDC

24 VDC

(20…30 VDC)

Power supply current ≤40 mA
OTHER
Basic accuracy ≤0,1 %
Sensor break signalization (max / min) LED
checkboxico/ checkboxico
LED
checkboxico/ checkboxico
Sensor linearization checkboxico checkboxico
Reversed output checkboxico¹ checkboxico
Input signal filtration checkboxico checkboxico
Galvanic isolation input / output
Galvanic isolation (test) 1500 VAC
Working temperature 0…70°C
Protection (housing / teminals) IP20 / IP20
Mounting DIN rail
CONFIG
Config DIP switch
OPTIONS
One / two-channel checkboxico/ — checkboxico/ —
Other input / output ranges (on request) checkboxico/ — checkboxico/ checkboxico
DOCUMENTS
Data sheet pdficoDownload pdficoDownload
¹according to the order
Back to top